Miami Facility unresponsive
Scheduled on 2019-06-08 13:57:00 Status Resolved Fault / IssueWe have lost communication with our Miami Facility. We are investigating
Related servers / services
MIA-04, PDNS2
Date | Action |
---|---|
2019-06-08 14:04:00 | We are awaiting a return on the investigation of the Onsite DC Team, since VPN and IPMI are not working to reach this facility. |
2019-06-08 15:04:00 | A Power Outage is affecting all the DC. We are awaiting an ETA + RFO since there should be UPS + Generator on-site. |
2019-06-08 15:55:00 | {"english":" A faulty input breaker has been detected for UPS-2. Electrical contractors are en route to the data center to transfer critical load to UPS-4 (Standby UPS). \r\n\r\nDatacenter tech has transfer the load temporary by doing a bypass. Service ar |
2019-06-08 22:00:00 | Load has been sucessfully transfered to new UPS. |
2019-06-08 22:23:00 | VPS are currently getting back online. |
2019-06-09 17:49:00 | Everything is back to normal avec 12h of monitoring. We close this task. |